RCM Direct Reading Flowmeters
RCM Direct Reading Flowmeters
 RCM Direct Reading Flowmeters

RCM Direct Reading Flowmeters

Special Features

  • Compact Design
  • Easy to Install
  • For Horizontal or Vertical Pipes
  • Rugged Construction
  • Accuracy: ± 3 % Full Scale
  • Rangeability 6:1
  • Flow Rates up to 3000 GPM Liquid or 20 000 SCFM Gas
  • Low Pressure Drop
  • Optional Alarms and Output Signals

Specifications:

  • Accuracy: ± 3% Full Scale
  • Measuring Ranges:
    • liquids: 0.5-4 GPH to 400-3000 GPM
    • Gases: 5-40 SCFH to 3000-20000 SCFM
  • Fittings: 1/4" - 3" NPT, 1/2" - 8" water
  • Material: Bronze, Monel or SS
  • Operating Temperature Range
    • Standard: -30 to 212 °F
    • Optional: -80 to 350 °F
  • Maximum Pressure
    • Standard: 180 PSIG
General Description

RCM Direct Reading Flowmeters

The RCM is a differential pressure direct reading flowmeter. It is suitable for monitoring all liquids and gases that have low or medium viscosity, low solids content, and are compatible with the materials of construction. The meter features rugged, compact construction. In liquid applications of 6 GPM and higher, pulsation snubbers are incorporated into the connecting pressure passages to produce smooth meter operation independent of pipeline turbulence.

This meter was developed for industrial flow metering applications in which durability and reliability are important considerations. Accuracy, small size, low cost, minimal maintenance and resistance to accidental damage are the prime goals in the RCM design. Typical applications include: lube oil and cooling water monitoring, blending processes, reverse osmosis systems, and compressed air measurement.

The RCM is available with a 4–20 mA output for interfacing with remote displays and controllers. Limit switches are available to provide high and low limit signals. A 0–1000 Hz frequency output is available to drive frequency based controllers and counters.

Specifications

Accuracy: ± 3% Full Scale
Flow Media: Liquids and Gases
Mounting: Horizontal or Vertical
Temperature Range
(Ambient and Process)
- Standard: – 30 to 212 °F
- Optional: – 80 to 350 °F
Maximum Pressure
- Standard: 180 PSIG
- Optional: 400 PSIG

Housing: Polycarbonate UV stabilized
Body: Bronze, Monel, or 316 SS
Option -ES: also TeflonTM
Bellows: Bronze, Monel 316 SS or InconelTM
Movement: Bronze or SS
Seals: Buna-N, Viton, EPDM or TeflonTM
Crystal: Polycarbonate
Relay Options: High/Low Alarms
Output Options: 4–20mA 0–1000 Hz Frequency
Ordering Information

Order RCM Series Flowmeter by:

  1. choose range and material for wetted part on order number tables
  2. choose options (if required)
  3. specify direction of flow according to Flow Direction instructions below.

Flow Direction:

  • R Horizontal, flow to right
  • L Horizontal, flow to left
  • VUR Vertical, flow up, dial at right
  • VDR Vertical, flow down, dial at right
  • VUL Vertical, flow up, dial at left
  • VDL Vertical, flow down, dial at left

Example:

RCM-7117-A-D-R is the catalog no. for a 3/4" NPT RCM Series 7000 Flowmeters of bronze construction, flow direction from left to right, flow rating of 20 GPM (full scale), equipped with optional seals of Viton and optional gasketed case.

Options (if required).

1S2
2S2
A
B
C
D
E
ES
G
H
K
N
O2
P
R
T
V
W
W2
W3
X
Y
Z
ingle SPDT Reed switch
Dual SPDT Reed switch
Viton seals
Customer-specified seals
Calibration for specific gravity
Gasketed case
Non-standard flow rate
Low flow rate
Custom scales and dials
400 psig service
Steam service (SS only)
Ammonia service
Oxygen cleaning
Panel mounting kit
LCD rate & total display
350 °F service rating
Calibration for high viscosity
4–20 mA dc
4–20 mA DP Transmitter
4–20 mA Blind DP Transmitter
Hi/Lo alarm relays
1000 Hz full scale frequency
Comb. of options W, X, Y

RCM Direct Reading Flowmeters
RCM Direct Reading Flowmeters

RCM Direct Reading Flowmeters

A minimum of 10 PSIG of back pressure is required for the RCM to be suitable for use with your application.
Order Numbers are a combination of the part number in the above table, and the Suffix designation for the desired options.
Example:
A 1/4" Monel unit for 0.4–3.0 GPM Water with Viton seals, flow right to left:
Order Number = RCM-7203 + A + L = RCM-7203-A-L.
When ordering, specify: Name of medium, viscosity and specific gravity if medium is other than water.

RCM Direct Reading Flowmeters

As with all RCM flowmeters, a minimum of 10 PSIG back pressure is required for proper operation.
Order Numbers are a combination of the part number in the above table, and the Suffix designation for the desired options.
Example:
A 1/2" Bronze unit for 4.0–30 SCFM Air at 400 PSIG and 350 °F, flow down at left:
Order Number = RCM-9106 + H + T + VDL = RCM-9106-H-T-VDL
When ordering, specify: Type of gas, operating inlet pressure and temperature.

RCM Direct Reading Flowmeters

Order Numbers are a combination of the part number in the above table, and the Suffix designation for the desired options.
Example:
A 4" Bronze unit for 800 GPM Water with Viton seals, flow up dial at right:
Order Number = RCM-5139 + A + VUR = RCM-5139-A-VUR
When ordering, specify: Name of medium, viscosity and specific gravity if medium is other than water.

RCM Direct Reading Flowmeters

RCM-5000 & 6000 series flowmeters are designed for wafer style mounting between two adjoining flanges. As with all model RCM meters, a minimum of 10 PSIG back pressure is required for operation. The meter will fit between all standard 150 lb or 300 lb ANSI flanges, DIN PN 10 or PN 16 flanges, JIS and AS flanges. Installation requires flanges, flat gaskets and flange bolts provided by the user.

Order Numbers are a combination of the part number in the above table, and the Suffix designation for the desired options.
Example:
A 6" Stainless Steel unit for 5000 SCFM Air with 4–20 mA transmitter and NEMA 4 gasketed case, flow to the right is:
Order Number = RCM-6338 + D2 + W-R = RCM-6338-D2-W-R.
When ordering, specify: Type of gas, operating inlet pressure and temperature.

Output Specifications

Output Combinations
Output options may be combined in any fashion desired. However, choice on an electronic output option does limit the choice of other options. In particular, choice of option W, W2, W3, X or Y, precludes the selection of the following options:

  • Option D: Gasketed Case
  • Option K: Steam Service
  • Option N: Ammonia Service
  • Option T: High Temperature
  • Option 1S2: Single SPDT Switch
  • Option 2S2: Dual SPDT Switch

General to All Output Options
Electrical Rating: Gen. Purpose
Power Requirements: 24 VDC ± 10%

Accuracy of Gauge with Outputs
Horizontal flow: ± 3% F. S.
Vertical flow: ± 5% F. S.

Maximum Temperature
Ambient: – 30 to 120 °F
Medium: – 30 to 212 °F

RCM Direct Reading Flowmeters

RCM Direct Reading Flowmeters

Dimensions

Output Options

The RCM offers five powered output configurations to allow connection to a variety of electronic process control equipment. The position of the indicator arm is read by a Hall sensor and translated into the required electrical signal:

  • Option W: 4–20 mA Flow Rate Transmitter
  • Option W2: 4–20 mA Differential Pressure Transmitter
  • Option W3: 4–20 mA Differential Pressure Transmitter w/o Indicator (Blind transmitter)
  • Option X: High and Low Alarm Relay Output
  • Option Y: 0–1000 Hz Frequency Output
  • Option Z: Options W, X & Y combined
RCM Direct Reading Flowmeters
RCM Direct Reading Flowmeters RCM Direct Reading Flowmeters

Output Specifications
Analog Output: Option W
Output
Signal: 4–20 mA Proportional to Flow
Load: 800 Ohms max.
Zero: 15% of Full Scale
Span: 30% to 100% of Full Scale Flow
Power: 24 VDC ± 10% 50 mA max.

Analog Output: Option W2/W3
Output: 4–20 mA Proportional to Differential Pressure
Load: 250 Ohms max.
Span: 15% to 100% of Full Scale Orifice Δ P
Power: 24 VDC ± 10%

 

Alarm Relays: Option X
Two N/O limit relays are provided; one relay is configured as a minimum and the other as a maximum. Red and green LEDs indicate relay operation.

Output: 2 N/O Limit Relays
Power: 24 VDC ± 10% 50 mA max.

Contact Rating

AC: 3.0 A @ 24 VAC
1.0 A @ 117 VAC
0.5 A @ 230 VAC
DC: 2.0 A @ 30 VDC
0.6 A @ 110 VDC
0.5 A @ 140 VDC

Frequency Output: Option Y
A 0–1000 Hz frequency output is available to drive pulse triggered controllers. The usable range is 30% to 100% of full scale flow.

Output: Frequency signal 0–1000 Hz 5 V peak
Zero: 15% of Full Scale
Span: 30% to 100% of Full Scale Flow
Power: 24 VDC ± 10% 50 mA max.

Dimensions of Wafer Style Meters

RCM Direct Reading Flowmeters
RCM Direct Reading Flowmeters

Wafer style RCM flowmeters are designed for mounting between two adjoining flanges. The meter will fit between all standard 150 lb or 300 lb ANSI flanges, DIN PN 10 or PN 16 flanges, JIS and AS flanges.

Installation requires flanges, flat gaskets and flange bolts provided by the user.